(MT) Compact transformer substations
2550
2350
4550
50Hz
IP 44
≤ 2000 m
'-35+35°C
≤ 100% (at +25°C)
Passive (natural convection) / Active (mechanical forced ventilation)
Designed for receiving 10 kV, 50 Hz electrical power and transforming it to 0.4 kV voltage for distribution to users; this is an outdoor service transformer substation connected to external networks via underground cables.
The substation consists of a reinforced concrete foundation and a metal enclosure with a removable roof. The substation is divided into six sections separated by partitions: two 10 kV compartments, two power transformer compartments, two 0.4 kV compartments.
LST EN 62271-202
10 kV
12 kV
28 kV
50 Hz
75 kV
External
Air or SF6 gas
Isolated
IP 3X
LSC2A
According to AB 'ESO' technical requirements
According to AB 'ESO' technical requirements
≥1000 A
25 kA
40 kA
One-sided - external
690 V
Installed are UAB 'ARMETLINA' VIN-10(NAL) or VIN-10(OMB) cubicles compliant with standard LST EN 62271-200, featuring 10 kV indoor power switches (LST EN 62271-1; LST EN 62271-102; LST EN 62271-103; LST EN 62271-105) according to AB 'ESO' requirements. Switchgear with SF6 gas insulation compliant with standards LST EN 62271-1, LST EN 62271-100, LST EN 62271-200, including ABB SAFE PLUS or SAFE RING, SCHNEIDER ELECTRIC RM6 or FBX, SIEMENS 8DJH switchgear.
Two prepared spaces with oil collection pits for three-phase hermetic oil transformers; (≤1500x1000x1800 mm) up to 630 kVA.
Two busbar sections; Two incoming fuse-switch blocks; Sectional fuse-switch block; Space for control metering; Space for commercial metering (KAS); Designated space for up to 8 linear fuse-switch blocks per section; Aluminum (Al) or Copper (Cu) busbars with pressed-in bushings (for convenient mounting of fuse-switch blocks); Auxiliary panel (SRS).
Transformer construction: 10 mm²; Doors: 4 mm².
Plug socket ~230V with grounding contacts, protected by RCCB and 1-phase C16A circuit breaker; 1-phase C6A circuit breaker for protection of 10 kV short-circuit indicator power supply; 1-phase C6A circuit breaker for lighting protection.
One location (three-phase) is allocated for the control electrical metering device and test terminal in the 0.4 kV distribution equipment compartment; upon order, current transformers are installed and connected.
The power transformer is loaded from the top by removing the roof. The transformer is placed on wheels into designated fixed positions that prevent movement. MV – Medium Voltage compartment with equipment; LV – Low Voltage compartment with equipment; KAS – Commercial metering.
armetlina.lt © 2024. All rights reserved.
To ensure the best experience, we use technologies such as cookies to store and/or access information on your device. Consent to these technologies allows us to process data such as browsing behavior or unique IDs. Without consent or if consent is withdrawn, some website features may not function properly.