MT-10/0.4-2 X 1000

Designed for receiving 10 kV, 50 Hz electrical power and transforming it to 0.4 kV voltage for distribution to users; this is an outdoor service transformer substation connected to external networks via underground cables.

Dimensions (H.W.D.), mm

Number of transformers

Transformer rated voltage MV/LV, kV

Transformer rated voltage MV/LV, kV

Rated frequency:

50Hz

Degree of protection:

Altitude above sea level:

Ambient temperature:

Relative humidity:

≤ 100% (at +25°C)

Ventilation:

Passive (natural convection) / Active (mechanical forced ventilation)

Standards:

LST EN 62271-202

10 kV section

10 kV Vardinė įtampa

10 kV

10 kV Maximum voltage:

12 kV

10 kV Test voltage (50Hz, 1 min):

28 kV

10 kV Rated frequency:

50 Hz

10 kV Impulse test voltage (1.2/50 μs):

75 kV

10 kV switchgear compartment maintenance:

External

10 kV Switchgear insulation:

Oras

10 kV Network neutral:

Isolated

10 kV Degree of protection:

IP3X

10 kV Service category:

LSC2A

10 kV Disconnectors

According to AB 'ESO' technical requirements

10 kV Surge arresters

According to AB 'ESO' technical requirements

0.4 kV section

0.4 kV rated busbar current

≥1600 A

0,4 kV šynų trumpo jungimo srovė

25 kA

0.4 kV busbar rated peak withstand current

40 kA

Maintenance of 0.4 kV section:

Vienpusis – išorinis

0.4 kV rated insulation voltage

690 V

MT dimensional drawing of two transformers with height (A), width (P) and depth (G) parameters marked.
MT drawing of the layout of the two transformers showing the MV and LV compartments and the location of the transformers (T).

MT-10/0.4-2 X 1000

Designed for receiving 10 kV, 50 Hz electrical power and transforming it to 0.4 kV voltage for distribution to users; this is an outdoor service transformer substation connected to external networks via underground cables.
Dimensions (H.W.D.), mm

Number of transformers

Transformer rated voltage MV/LV, kV

Transformer rated voltage MV/LV, kV

Rated frequency:

50Hz

Degree of protection:

Altitude above sea level:

Ambient temperature:

Relative humidity:

≤ 100% (at +25°C)

Ventilation:

Passive (natural convection) / Active (mechanical forced ventilation)

Standards:

LST EN 62271-202

10 kV section

10 kV Vardinė įtampa

10 kV

10 kV Maximum voltage:

12 kV

10 kV Test voltage (50Hz, 1 min):

28 kV

10 kV Rated frequency:

50 Hz

10 kV Impulse test voltage (1.2/50 μs):

75 kV

10 kV switchgear compartment maintenance:

External

10 kV Switchgear insulation:

Oras

10 kV Network neutral:

Isolated

10 kV Degree of protection:

IP3X

10 kV Service category:

LSC2A

10 kV Disconnectors

According to AB 'ESO' technical requirements

10 kV Surge arresters

According to AB 'ESO' technical requirements

0.4 kV section

0.4 kV rated busbar current

≥1600 A

0,4 kV šynų trumpo jungimo srovė

25 kA

0.4 kV busbar rated peak withstand current

40 kA

Maintenance of 0.4 kV section:

Vienpusis – išorinis

0.4 kV rated insulation voltage

690 V

Basic Information

Enclosure:

The substation consists of a reinforced concrete foundation and a metal enclosure with a removable roof. The substation is divided into six sections separated by partitions: two 10 kV compartments, two power transformer compartments, two 0.4 kV compartments.

Additional information

Medium voltage:

Sumontuoti su hermetizuoto oro vidutinės įtampos skirstyklomis; vieta TSPĮ.

Transformer:

"Two prepared spaces with oil collection pits for three-phase hermetic oil transformers; (≤1500x1000x1800 mm) up to 1000 kVA.

Low voltage:

Two busbar sections; Two incoming fuse-switch blocks; Sectional fuse-switch block; Space for control metering; Space for commercial metering (KAS); Designated space for up to 8 linear fuse-switch blocks per section; Aluminum (Al) or Copper (Cu) busbars with pressed-in bushings (for convenient mounting of fuse-switch blocks); Auxiliary panel (SRS).

Grounding conductors:

Transformer construction: 10 mm²; Doors: 4 mm².

Internal use panel

Plug socket ~230V with grounding contacts, protected by RCCB and 1-phase C16A circuit breaker. 1-phase C6A circuit breaker for protection of 10 kV short-circuit indicator power supply. 1-phase C6A circuit breaker for lighting protection.

Verification metering

One location (three-phase) is allocated for the control electrical metering device and test terminal in the 0.4 kV distribution equipment compartment; upon order, current transformers are installed and connected.

Equipment details:

The power transformer is loaded from the top by removing the roof. The transformer is placed on wheels into designated fixed positions that prevent movement. MV – Medium Voltage compartment with equipment; LV – Low Voltage compartment with equipment; KAS – Commercial metering.