MT(m)-10/0.4-1 X 630

Designed for receiving 10 kV, 50 Hz electrical power and transforming it to 0.4 kV voltage for distribution to users; this is an outdoor service transformer substation connected to external networks via underground cables.

Dimensions (H.W.D.), mm

Weight without power transformer, kg

≤ 4700

Number of transformers

Transformer rated voltage MV/LV, kV

Transformer rated voltage MV/LV, kV

Degree of protection (IP)

IP43

Altitude above sea level

≤ 2000 m

Ambient temperature

-35…+40°C

Relative humidity

≤ 100% (at +25°C)

Ventilation

Passive (natural convection) / Active (mechanical forced ventilation)

Standards

LST EN 62271-202

10 kV section

—

10 kV Vardinė įtampa

10 kV

10 kV Maximum voltage:

12 kV

10 kV Test voltage (50Hz, 1 min):

28 kV

10 kV Vardinis dažnis, Hz

50 Hz

10 kV Impulse test voltage (1.2/50 μs):

75 kV

10 kV switchgear compartment maintenance:

External

10 kV Switchgear insulation:

Air insulation

10 kV Network neutral:

Isolated

10 kV Degree of protection:

IP3X

10 kV Service category:

LSC2A

10 kV Disconnectors

According to AB 'ESO' technical requirements

10 kV Surge arresters

According to AB 'ESO' technical requirements

0.4 kV section

—

0.4 kV rated busbar current

≥1000 A

0,4 kV šynų trumpo jungimo srovė

25 kA

0.4 kV busbar rated peak withstand current

40 kA

Maintenance of 0.4 kV section:

Vienpusis – išorinis

0.4 kV rated insulation voltage

690 V

Drawing for small transformers height (A), width (P), depth (G)
Single transformer modular transformer room layout diagram: T - transformer, LV compartment, MV compartment, TSPA and CSA areas with door directions marked

MT(m)-10/0.4-1 X 630

Product category:
Designed for receiving 10 kV, 50 Hz electrical power and transforming it to 0.4 kV voltage for distribution to users; this is an outdoor service transformer substation connected to external networks via underground cables.
Dimensions (H.W.D.), mm

Weight without power transformer, kg

≤ 4700

Number of transformers

Transformer rated voltage MV/LV, kV

Transformer rated voltage MV/LV, kV

Degree of protection (IP)

IP43

Altitude above sea level

≤ 2000 m

Ambient temperature

-35…+40°C

Relative humidity

≤ 100% (at +25°C)

Ventilation

Passive (natural convection) / Active (mechanical forced ventilation)

Standards

LST EN 62271-202

10 kV section

—

10 kV Vardinė įtampa

10 kV

10 kV Maximum voltage:

12 kV

10 kV Test voltage (50Hz, 1 min):

28 kV

10 kV Vardinis dažnis, Hz

50 Hz

10 kV Impulse test voltage (1.2/50 μs):

75 kV

10 kV switchgear compartment maintenance:

External

10 kV Switchgear insulation:

Air insulation

10 kV Network neutral:

Isolated

10 kV Degree of protection:

IP3X

10 kV Service category:

LSC2A

10 kV Disconnectors

According to AB 'ESO' technical requirements

10 kV Surge arresters

According to AB 'ESO' technical requirements

0.4 kV section

—

0.4 kV rated busbar current

≥1000 A

0,4 kV šynų trumpo jungimo srovė

25 kA

0.4 kV busbar rated peak withstand current

40 kA

Maintenance of 0.4 kV section:

Vienpusis – išorinis

0.4 kV rated insulation voltage

690 V

Compartment layout and installation:

The power transformer is lifted in from the top after removing the roof. The transformer, fitted with wheels (rollers), is placed into designated fixing positions that prevent the transformer from moving.
MV - (Eng. medium voltage) medium voltage compartment with equipment;
LV - (Eng. low voltage) low voltage compartment with equipment;
KAS - Commercial metering (tariff metering).

Enclosure:

Transformatorinę sudaro gelžbetoninis pamatas ir metalinis korpusas su nukeliamu stogu. Transformatorinė susideda iš trijų pertvaromis atskirtų dalių:
10 kV skyrius, galios transformatoriaus skyrius, 0,4 kV skyrius.

Medium voltage:

To be equipped with hermetically sealed air-insulated medium-voltage switchgear; space for an RTU provided.

Transformer:

Paruoštos vieta su alyvos surinkimo duobe , trijų fazių, hermetiškam alyviniam transformatoriui; (≤1500x1000x1800) iki 630kVA galios.

Low voltage:

Įvadinis saugiklių-kirtiklių blokas; Vieta kontrolinei apskaitai; Vieta komercinei apskaitai (KAS); Numatyta vieta linijiniams saugiklių-kirtiklių blokams, iki 6 vnt. ; Šynos Al su įpresuotomis įvorėmis (patogiam kirtiklių saugiklių blokų montavimui); Vieta generatoriaus pajungimui; Savų reikmių skydas (SRS)

Grounding conductors:

Transformer construction: 10 mm²; Doors: 4 mm².

Auxiliary power supply cabinet (SRS):

Plug socket ~230V with grounding contacts, protected by RCCB and 1-phase C16A circuit breaker; 1-phase C6A circuit breaker for protection of 10 kV short-circuit indicator power supply; 1-phase C6A circuit breaker for lighting protection.

Verification metering

Numatyta 1 vieta (trijų fazių) kontroliniam elektros apskaitos prietaisui ir bandymų gnybtui 0,4 kV paskirstymo įrenginių skyriaus dalyje, užsakius: srovės transformatoriai sumontuojami ir prijungiami.