MT(M) Small compact transformer substation
| Dimensions (H.W.D.), mm | |
|---|---|
| Number of transformers | |
| Transformer rated voltage MV/LV, kV | |
| Transformer rated voltage MV/LV, kV | |
| Degree of protection: | |
| Altitude above sea level: | |
| Ambient temperature: | |
| Relative humidity: | ≤ 100% (at +25°C) | 
| Ventilation: | Passive (natural convection) / Active (mechanical forced ventilation) | 
| Standards: | LST EN 62271-202 | 
Designed for receiving 10 kV, 50 Hz electrical power and transforming it to 0.4 kV voltage for distribution to users; this is an outdoor service transformer substation connected to external networks via underground cables.
The substation consists of a reinforced concrete foundation and a metal enclosure with a removable roof. The substation is divided into three sections separated by partitions: 10 kV compartment, power transformer compartment, 0.4 kV compartment.
10kV
12kV
28kV
50Hz
75kV
External
Air ; SF6 gas
Isolated
IP3X
LSC2A
According to AB 'ESO' technical requirements
According to AB 'ESO' technical requirements
≥250 A
25kA
40kA
One-sided - external
690V
Installed by SCHNEIDER ELECTRIC RM6 cages, but other ABB SafeRing, SafePlus, SCHNEIDER ELECTRICAL FBX, SIEMENS 8DJH cages conforming to LST EN 62271- 200 can be installed.
Prepared space with an oil collection pit (≤530 liters) for a three-phase hermetic oil transformer (≤1200x870x1400 mm) up to 160 kVA power.
Incoming fuse-switch block; Space for control metering; Space for commercial metering (KAS); Designated space for up to 3 linear fuse-switch blocks; Aluminum busbars with pressed-in bushings (for convenient mounting of fuse-switch blocks); Space for generator connection; Auxiliary panel (SRS); Space for TSPĮ panel installation.
Transformer construction: 10 mm²; Doors: 4 mm².
Plug socket ~230V with grounding contacts, protected by RCCB and 1-phase C16A circuit breaker; 1-phase C6A circuit breaker for protection of 10 kV short-circuit indicator power supply; 1-phase C6A circuit breaker for lighting protection; 1-phase C16 circuit breaker for protection of TSPĮ equipment power supply.
One location (three-phase) is allocated for the control electrical metering device and test terminal in the 0.4 kV distribution equipment compartment; upon order, current transformers are installed and connected.
The power transformer is loaded from the top by removing the roof. The transformer is placed on wheels into designated fixed positions that prevent movement. MV – Medium Voltage compartment with equipment; LV – Low Voltage compartment with equipment; KAS – Commercial metering.
To ensure the best experience, we use technologies such as cookies to store and/or access information on your device. Consent to these technologies allows us to process data such as browsing behavior or unique IDs. Without consent or if consent is withdrawn, some website features may not function properly.