MT-10/0.4-2 X 1600

(MT) Compact transformer substations

Basic Information

Height (mm):

2900

Width (mm):

5800

Depth (mm):

3600

Techniniai parametrai

Rated frequency:

50Hz

Degree of protection:

IP 44

Altitude above sea level:

≤ 2000 m

Ambient temperature:

'-35+35°C

Relative humidity:

≤ 100% (at +25°C)

Ventilation:

Passive (natural convection) / Active (mechanical forced ventilation)

Basic Information

Description

Designed for receiving 10 kV, 50 Hz electrical power and transforming it to 0.4/0,8 kV voltage for distribution to users; this is an outdoor service transformer substation connected to external networks via underground cables.

Enclosure:

The substation consists of a reinforced concrete foundation and a metal enclosure with a removable roof. The substation is divided into six sections separated by partitions: two 10 kV compartments, two power transformer compartments, two 0.4/0.8 kV compartments.

Standards:

LST EN 62271-202

10 kV voltage compartment

Rated voltage: 10 kV

10 kV

Maximum voltage:

12 kV

Test voltage (50Hz, 1 min):

28 kV

Rated frequency:

50 Hz

Impulse test voltage (1.2/50 μs):

75 kV

switchgear compartment maintenance:

External

Gas-Insulated Switchgear insulation:

Air or SF6 gas

Network neutral:

Isolated

Degree of protection:

IP 3X

Service category:

LSC2A

0.4 kV voltage compartment

Rated current of 0.4 kV busbars:

≥1600 A

Short-circuit current of 0.4 kV busbars:

25 kA

Peak short-circuit current of 0.4 kV busbars:

40 kA

Maintenance of 0.4 kV section:

One-sided - external

Additional information

Medium voltage:

Installed with SF6 gas insulation, compliant with standards LST EN 62271-1, LST EN 62271-100, LST EN 62271-200, ABB SAFE PLUS or SAFE RING, SCHNEIDER ELECTRIC RM6 or FBX, SIEMENS 8DJH switchgear; location for mounting the TSPĮ panel.

Transformer:

Paruoštos dvi vietos su alyvos surinkimo duobėmis , trijų fazių, hermetiškiems alyviniams transformatoriams; (≤1500x1000x1800mm) iki 1600 kVA.

Low voltage:

Two busbar sections; Two incoming fuse-switch blocks and/or automatic circuit breakers; Sectional fuse-switch block and/or automatic circuit breaker; Space for control metering; Space for commercial metering (KAS); Designated space for linear fuse-switch blocks and/or automatic circuit breakers; Aluminum (Al) or Copper (Cu) busbars with pressed-in bushings (for convenient mounting of fuse-switch blocks); Auxiliary panel (SRS).

Grounding conductors:

Transformer construction: 10 mm²; Doors: 4 mm².

Internal use panel

Plug socket ~230V with grounding contacts, protected by RCCB and 1-phase C16A circuit breaker; 1-phase C6A circuit breaker for protection of 10 kV short-circuit indicator power supply; 1-phase C6A circuit breaker for lighting protection; 1-phase C16 circuit breaker for protection of TSPĮ equipment power supply.

Verification metering

One location (three-phase) is allocated for the control electrical metering device and test terminal in the 0.4/0,8 kV distribution equipment compartment; upon order, current transformers are installed and connected.

Equipment details:

The power transformer is loaded from the top by removing the roof. The transformer is placed on wheels into designated fixed positions that prevent movement. MV – Medium Voltage compartment with equipment; LV – Low Voltage compartment with equipment; KAS – Commercial metering.