ĮEAS – 318

Designed to connect an electricity consumer to a three-phase/single-phase 400 V / 230 V, 50 Hz power grid; suitable for operation only inside apartment buildings; the sealable metering module is designed to accommodate all types of direct-connected electricity meters.

Dimensions (H.W.D.), mm

Number of meters

Rated operational voltage (Ue)

~230/400V

Rated frequency (fn)

50 Hz

Rated insulation voltage (Ui)

690V

Rated impulse withstand voltage (Uimp)

6 kV

Rated current of the assembly (InA)

100 A, 63 A

Rated short-time withstand current (Icw)

≤ 10kA (for 1s)

Rated peak withstand current (Ipk)

12 kA

Degree of protection (IP)

IP44

Mechanical impact resistance (IK)

IK10

Protection against electric shock

Class I

Ventilation

Passive

Intended location

Vidaus patalpose

Mounting

Ant cokolio

Enclosure:

Cinkuotas lakštinis plienas DX51D+Z275, storis 1.5 mm.

Altitude above sea level

≤ 2000 m

Ambient temperature

-35…+40°C

Relative humidity

≤ 100% (at +25°C)

Standards

LST EN 61439-1, LST EN 61439-5

You may also like…

ĮEAS-318 electrical schematic

ĮEAS – 318

Designed to connect an electricity consumer to a three-phase/single-phase 400 V / 230 V, 50 Hz power grid; suitable for operation only inside apartment buildings; the sealable metering module is designed to accommodate all types of direct-connected electricity meters.
Dimensions (H.W.D.), mm

Number of meters

Rated operational voltage (Ue)

~230/400V

Rated frequency (fn)

50 Hz

Rated insulation voltage (Ui)

690V

Rated impulse withstand voltage (Uimp)

6 kV

Rated current of the assembly (InA)

100 A, 63 A

Rated short-time withstand current (Icw)

≤ 10kA (for 1s)

Rated peak withstand current (Ipk)

12 kA

Degree of protection (IP)

IP44

Mechanical impact resistance (IK)

IK10

Protection against electric shock

Class I

Ventilation

Passive

Intended location

Vidaus patalpose

Mounting

Ant cokolio

Enclosure:

Cinkuotas lakštinis plienas DX51D+Z275, storis 1.5 mm.

Altitude above sea level

≤ 2000 m

Ambient temperature

-35…+40°C

Relative humidity

≤ 100% (at +25°C)

Standards

LST EN 61439-1, LST EN 61439-5

Enclosure:

Galvanized sheet steel DX51D+Z275, 1.5 mm thick, painted in standard RAL7032 color (other options available according to the project).