KP-6/10

Product category:

Medium voltage 6–10 kV switching station

Transformer rated voltage MV/LV, kV
Transformer rated power, kVA
Number of transformers
Nominal voltage:

≤ 10kV

Rated frequency:

50Hz

Degree of protection:

Altitude above sea level:

Ambient temperature:

Relative humidity:

≤ 100% (at +25°C)

Ventilation:

Passive (natural convection) / Active (mechanical forced ventilation)

Standards:

LST EN 62271-202

Basic Information

Description

Designed for receiving and distributing 6–10 kV, 50 Hz electrical power using switching devices; Installed medium voltage equipment configurable with linear power switch compartments, linear vacuum switch compartments, and compartments with measuring transformers for commercial metering; This is an outdoor service device connected to external networks via underground cables; Complies with AB ‘ESO’ technical requirements.

Enclosure:

The KP consists of a reinforced concrete foundation and a metal enclosure with a removable roof. The KP is divided into two sections separated by partitions: a 6–10 kV compartment and a control compartment.

10 kV voltage compartment

Rated voltage: 10 kV

10 kV

Maximum voltage:

12 kV

Test voltage (50Hz, 1 min):

28kV

Rated frequency:

50Hz

Impulse test voltage (1.2/50 μs):

75kV

switchgear compartment maintenance:

External

Gas-Insulated Switchgear insulation:

Air or SF6 gas

Degree of protection:

IP3X

Service category:

LSC2A

Switchgear

According to AB 'ESO' technical requirements

Surge arresters:

According to AB 'ESO' technical requirements

Additional information

Medium voltage:

Fitted with SF6 gas insulation standards LST EN 62271-1, LST EN 62271-100, LST EN 62271-200 compliant ABB SAFE PLUS or SAFE RING, SCHNEIDER ELECTRICRM6 or FBX, SIEMENS 8DJH switchgear; space for installation of the TSPA panel.

Low voltage:

Self-use shield (SRS).

Internal use panel

Socket ~230V with earth contacts, protected by RCCB and auto switch 1f C16A; Auto switch 1f C6A for power protection of 10kV short circuit indicators; Auto switch 1f C6A for protection of luminaires; Auto switch 1f C16 for power protection of TSPĮ equipment.